C Alarm List
Alarm
ID
(Alarm
ID-Caus
e ID)
Cable
connectio
ns are
incorrect.
The mains
is not
normal.
The
power
module is
faulty.
1. Check whether cables to mains
are disconnected, loose, or
incorrectly connected.
2. If cable connections are correct,
measure the mains voltage with
a multimeter. If the mains
voltage exceeds 280 V, the
mains input is not normal; if the
mains voltage is less than 272
V, the sampling circuit of the
power module is not normal.
Replace the faulty module.
Cable
connectio
ns are
incorrect.
The mains
is not
normal.
The mains
input fuse
for the
power
module is
blown.
1. Check whether cables to mains
are disconnected, loose, or
incorrectly connected.
2. If cable connections are correct,
measure the mains voltage with
a multimeter. If the mains
voltage is less than 80 V, the
mains voltage is not normal; if
the mains voltage exceeds 88 V,
the power module sampling
circuit or fuse may not be
working properly. Replace the
faulty module.
Cable
connections
are incorrect.
Verify the cable connections.