UPS5000-E-(50 kVA-300 kVA) 
User Manual (50 kVA Power Modules) 
 
Huawei Proprietary and Confidential                                     
Copyright © Huawei Technologies Co., Ltd. 
 
Alarm 
ID 
(Alarm 
ID-Caus
e ID) 
length of 
the bypass 
input or 
output 
cables is 
incorrect. 
 
The 
bypass 
SCR 
open-circ
uits. 
3.  Rectify any bypass SCR 
open-circuit. 
 
The 
bypass 
frequency 
changes 
fast. 
 
The 
output 
frequency 
track rate 
is 
incorrectl
y set. 
1.  Check that the bypass output 
frequency does not change fast. 
2.  Check that the Output freq. 
track rate is properly set. 
 
The dual 
bus 
connector 
is loose. 
 
Parameter
s are set 
incorrectl
y. 
1.  Check the dual bus connector. 
2.  Check the parameter settings. 
Maint. 
breaker 
misoperatio
n 
The user 
operation is 
incorrect. 
1.  Shut down the inverter and then 
close the maintenance circuit 
breaker. 
2.  After maintenance, open the 
maintenance circuit breaker and 
then start the inverter. 
The inverter 
is in 
self-check. 
Wait until the inverter self-check is 
complete.