UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
51
Table 3-7 Upstream input switch configurations
Upstrea
m
Input
Switch
UPS5000-E-200K-SM/FM
UPS5000-E-300K-SM/S
MT
50 kVA
100 kVA
150 kVA
200 kVA
250 kVA
300 kVA
Mains
input
160 A/3P
250 A/3P
320 A/3P
400 A/3P
630 A/3P
630 A/3P
Bypass
input
100 A/3P
160 A/3P
250 A/3P
400 A/3P
400 A/3P
630 A/3P
Table 3-8 Recommended upstream input and downstream output circuit breakers
Model
UPS
Capacity
Component
Specification
s
Manufactur
er
UPS5000-E-2
00K-SM/FM
50 kVA
Mains input circuit
breaker
T1N160 TMD
R160 FFC 3P
ABB
(recommende
d when the
short-circuit
current where
the switch is
located is
less than 36
kVA.)
Bypass input circuit
breaker
T1N160 TMD
R100 FFC 3P
Downstream output
circuit breaker
T1N160 TMD
R100 FFC 3P
100 kVA
Mains input circuit
breaker
T3N250 TMD
R250 FF 3P
Bypass input circuit
breaker
T1N160 TMD
R160 FFC 3P
Downstream output
circuit breaker
T1N160 TMD
R160 FFC 3P
150 kVA
Mains input circuit
breaker
T5N400 TMA
R320 FF 3P
Bypass input circuit
breaker
T3N250 TMD
R250 FF 3P
Downstream output
circuit breaker
T3N250 TMD
R250 FF 3P
200 kVA
Mains input circuit
breaker
T5N400 TMA
R400 FF 3P
Bypass input circuit
breaker
T5N400 TMA
R400 FF 3P
Downstream output
circuit breaker
T5N400 TMA
R400 FF 3P
UPS5000-E-3
00K-SM/FM
T
250 kVA
Mains input circuit
breaker
T6N630
PR221DS-LS/
I R630 FF 3P