1 2 3 4
Freeze-Clik
®
Hunter SRC Controller
CRS
Connect Common to
this Terminal when
using Rain Sensor
Connect Rain
Sensor Wires to
These Two Terminals
Solenoid
Va
lves
Fig. 2 
Freeze-Clik
®
Hunter ICC
Hunter Pr
o-C
Controller
SEN
SEN
C
TEST
P MV
Fig. 3 
To Solenoid
Va
lves
Mini-Clik
®
Freeze-Clik
®
1 2 3 4
Controller
C
Common Wire
Fig. 5 
1 2 3 4
Freeze-Clik
®
Controller
C
Common Wire to
All Va
lves
To Solenoid
Va
lves
Fig. 4 
22
If the best location 
for temperature sens-
ing is not a feasible 
location for mounting 
the Freeze-Clik
®
, an al-
ternate location may be 
chosen if, in addition, 
a “sun guard” is used 
(a piece of flashing, for 
example) to shade the 
Freeze-Clik during that 
time of day that the sun 
could hit it (see Fig. 1).
The Freeze-Clik housing is designed so that it 
provides the sensing element some amount of shaded 
protection from direct or indirect radiation, while al-
lowing air to move freely around it. Using the screws 
provided, attach the Freeze-Clik to the chosen surface. 
Run the extension wire to the controller.
Wiring
Wiring to the Hunter SRC Controller
The Freeze-Clik connects directly to the SRC. This 
allows you to easily override the sensor by using the 
RUN (BYPASS SENSOR) position on the dial.
1.  Route the 
wires from the 
Freeze Clik up 
through the same 
opening used for 
valve wiring.
2.  Connect one wire 
to the RS termi-
nal and other to 
the C terminal 
(See Fig. 2).
3.  Connect the valve common to the RS terminal.
Wiring to the Hunter ICC, Pro-C and 
EC Controller
The Freeze-Clik connects directly to the ICC, Pro-C 
and EC. This allows you to easily override the sensor 
by using the Sensor switch on the front panel.
1.  Remove the jumper from the two “SEN” terminals.
2.  Route the wires from the rain sensor up through the 
same conduit opening used for valve wiring.
3.  Connect one wire 
to the terminal 
labeled “SEN” 
and the other 
wire to the other 
“SEN” terminal 
(See Fig. 3).
Other Controllers
The Freeze-Clik 
freeze sensor is wired 
to the 24 VAC com-
mon ground circuit of 
the solenoid valves 
(as shown in Fig. 4). 
Locate the common 
ground wire of the 
solenoid valves. If it 
is connected to the 
common terminal on 
the controller, discon-
nect it.
Attach one lead of 
the Freeze-Clik to the 
common terminal on 
the controller and the 
other lead to the com-
mon ground wire of 
the solenoid valves.
If a Mini-Clik
®
 
rain sensor is already 
installed or is to be 
part of the installation 
(see Fig. 5), the freeze sensor is to be wired in series 
with the rain sensor so that either (or both) devices can 
control the circuit.
Operation
The Freeze-Clik is preset and is not adjustable. It will 
break the common ground circuit, thereby keeping 
the sprinkler system from operating at, or below, 3˚C 
(37˚F). At temperatures above 3˚C, it will close the 
circuit for normal sprinkler operation.
Freeze-Clik-Rev Model: The temperature setting 
works in reverse on this model with the circuit not 
allowing operation of the sprinkler system above 3˚C 
(37˚F). Once the temperature reaches this point or goes 
below, it will activate the system and commence water-
INSTALLATION INSTRUCTIONS (continued)