SECTION 3
Pr.12.3 NoOfDecimal Number of decimal places (D = 2 dec points)
The number of decimal places required for displaying when in normal operation.
Options displayed
Description
12.3.1 Display No decimal point Display value with no decimal point
12.3.2 Display 1 Decimal Point Display value with 1 decimal point
12.3.3 Display 2 Decimal Points Display value with 2 decimal points
12.3.4 Display 3 Decimal Points Display value with 3 decimal points
Pr.12.4 Relay tot. Relay totaliser (D = Off)
Options displayed Description
12.4.1 Relay totaliser off Disables relay totaliser function
12.4.2 Relay totaliser on Enable relay totaliser function
Pr.12.5
Simulation (D = No)
Options displayed
Description
12.5.1 Simulation No Don’t simulate program
12.5.2 Simulation Yes Start simulation
The value displayed will depend on the application set in Pr.1.0.
Select
12.5.2 Simulation Yes to simulate the operation of the instrument as set up
between Blanking (Pr.4.0) and Empty distance (Pr.2.0).
Application type
Display value relative to
Level Measurement - LEVEL
Distance measurement - DISTANCE
Differential level measurement - NO SIMULATION AVAILABLE
Open Channel Measurement - LEVEL
Pump Control - LEVEL
Volume - LEVEL
It will set all LEDs/relays and the current output as programmed. Therefore, care
must be taken if the instrument is wired into other instruments or controls. The
displayed value, on which all relays are operated, is that which is set by the operator.
The initial speed of the simulation is that set into Rate of Change (Pr.5.0) this can be
increased by a factor of 2 by pressing the ' ' key and the key can be pressed 6 times
(x64). To reduce the speed press the ' ' key, the speed cannot be reduced below
that defined by Rate of Change.
The direction of the simulation can be changed by using the ' ' and 'ENT' keys,
which one has to be pressed depends on the set up. Press ' M' to end.
Ref: MINIFLEX LR MANUAL Rev. 0 33