SETUP
powermax600
Operator Manual 3-3
Power Hookup (Continued)
Install Power Cord Plug
Use a power cord plug that is certified by national or local
electrical codes. The plug should be connected to the
power cord by a licensed electrician.
Extension Cord
Use a cord that is certified by national or local codes. The cord should be installed by a licensed electrician. Refer
to the length requirements listed below.
< 10 ft 10-25 ft 25-50 ft 50-100 ft 100-150 ft
< 3 m 3 – 7.5 m 7.5 – 15 m 15 – 30 m 30 – 45 m
Input-
Voltage Phase Recommended Cord Gauge Size (mm
2
)
208-240 VAC 1 10 10 10 16 16
230 VAC 3 4 6 6 10 10
400 VAC 3 2.5 2.5 4 6 6
480 VAC 3 4 4 4 4 6
Recommended Cord Gauge Size (AWG)
208-240 VAC 1 8 8 8 6 6
230 VAC 3 12 10 10 8 8
400 VAC 3 14 14 12 10 10
480 VAC 3 12 12 12 12 10