Attention: The overpressure safety device must meet the following requirements:
v Comply with ISO 4126-1. For more information, go to the ANSI Standards Store
website (webstore.ansi.org/default.aspx), and search on document number ISO
4126–1.
v Be installed so that it is easily accessed for inspection, maintenance, and repair
v Be connected as close as possible to the device that it is intended to protect
v Be adjustable only with the use of a tool
v Have a discharge opening that is directed so that discharged water or fluid does
not create a hazard or directed toward any person
v Be of adequate discharge capacity to ensure that the maximum working pressure
is not exceeded
v Be installed without a shutoff valve between the overpressure safety device and
the protected device
Figure 24 on page 81 shows a typical cooling solution and identifies the
components of the primary cooling loop and secondary cooling loop.
Figure 23 on page 80 shows an example of a fabricated facilities solution. The
actual number of heat exchangers that are connected to a secondary loop depends
on the capacity of the cooling distribution unit that is running the secondary loop.
Figure 21 on page 78 shows an example of an off-the-shelf modular cooling
distribution unit. The actual number of heat exchangers that are connected to a
secondary loop depends on the capacity of the cooling distribution unit that is
running the secondary loop.
Figure 22 on page 79 shows an example of a water-chiller unit that supplies
conditioned water to one or more heat exchangers. This water-chiller unit must be
a closed system (no exposure of the water to air) and meet all materials, water
quality, water treatment, and temperature and flow specifications that are defined
in this document. A water chiller unit is considered an acceptable alternative to use
as a building chilled water source for removing heat from the rear-door heat
exchanger.
Chapter 10. Planning for the rear-door heat exchanger 77

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM XIV Gen3 Series and is the answer not in the manual?

IBM XIV Gen3 Series Specifications

General IconGeneral
BrandIBM
ModelXIV Gen3 Series
CategoryStorage
LanguageEnglish

Related product manuals