Specications
Icon Descriptions
Fan operation icon
Cooling operation icon
Heating operation icon
Lock mode
activated
Room
temperature
offset activated
Electrical rating: 24 VAC (18-30 VAC)
1 amp maximum per terminal
3 amp maximum total load
Temperature control range: 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C)
System configurations: 1-stage heat, 1-stage cool, heat pump, gas, oil, electric
Timing:
Anti-short Cycle:
4 minutes
Backlight Operation
Terminations: S1, S2, Y, W/O/B, G, RC, RH, C