18 Innovative Circuit Technology Ltd.
SNMPv3 Settings:
User Name: Enter the user name for SNMPv3 access.
Authentication Protocol: Select the SNMPv3 authentication protocol
(None, MD5, or SHA).
Authentication Password: If an authentication protocol is selected,
enter the authentication password.
Privacy Protocol: Select the SNMPv3 privacy protocol (None, or AES).
Privacy Password: If a privacy protocol is selected, enter the privacy
password.
SNMP Trap Settings:
Trap Version: Sets the SNMP version (v1 or v3) for SNMP traps sent
from the PDU. The appropriate settings for the selected SNMP version
will need to be configured.
Trap Community: Assign the community string/password that will be
sent with all SNMPv1 traps. Some trap receivers are able to filter based
on Trap Community.
Trap User Name: Assign the user name for SNMPv3 traps.
Authentication Protocol: Select the authentication protocol for SNMPv3
traps (None, MD5, or SHA).
Authentication Password: If an authentication protocol is selected,
enter the authentication password for SNMPv3 traps.
Privacy Protocol: Select the privacy protocol for SNMPv3 traps (None, or
AES).
Privacy Password: If a privacy protocol is selected, enter the privacy
password for SNMPv3 traps.
Trap IP Addresses: Enter the IP addresses for up to two devices that will
receive SNMP traps from the PDU.