EasyManua.ls Logo

Idex Class 1 ITL 40 - Using the Display to Verify Pressure Sensor Signal Voltage

Idex Class 1 ITL 40
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FORM-ENG-0018 REV A 05-27-03
607 NW 27th Ave
Ocala, FL 34475
Ph: 352-629-5020 or 1-800-533-3569
Fax : 352-629-2902 or 1-800-520-3473
S U I T A B L E F O R E X T E R N A L D I S T R I B U T I O N
OPERATION MANUAL
PAGE
25 of 27
DATE
6/12/2019
PRODUCT GROUP
ITL40
P/N
REV
1.30
PRODUCT
Intelli-Tank Level 40
BY
AMS
MANUAL P/N:118253 PRINTED: 6/12/19
Condition
Visual
Evaluate
No passwords are
accepted.
If the display flashes “X” four times after entering a password, insure the display is
installed right side up. During power-up the display should turn on all LEDs and
then cycle them OFF starting with the top row, then the display should scroll the
custom greeting from right to left.
Check that the left and right magnetic switches are recognized by activating each
switch and verifying that the associated LEDs illuminate.
The bottom four LED
rows are on and
occasionally they go out
and the top four LED
rows flash and then
return to the bottom four
LED rows on (or vice-
versa). (REMOTE).
Check for large noise spikes on the 1-wire data line.
Insure that the display’s ground potential is the same as the MASTER’s.
Insure that the data line is not chaffed and making contact with other electrical
wires.
The points calibrated
seemed to have
changed.
No picture
Check the pressure sensor for problems.
Recalibrate the display and take a voltage reading from the sensor (pin 6 on the
display’s connector) at each calibration point. When the calibration points again
look wrong check the voltages at those points and determine if they are the same
as the voltage reading taken during calibration if they are not then replace the
sensor.
Unit will not dim display.
No picture
Insure the Dim input voltage on Pin 4 is at least 9V. Recalibrate dim setting
(RLLR LLLR). If display does not dim LEDs while in the dim configure mode,
replace display.
The middle two LED
rows are flashing
together.
A calibration was started on the display but not completed correctly. Set the
display to a REMOTE display (LRLR LRLR) or calibrate it as a MASTER (follow
calibration steps exactly).
LEDs cycle ON toward
the center continuously.
The display has had a unit type memory error.
Attempt to set the display back to REMOTE or MASTER as required.
Replace the display if this error cannot be corrected.
7.2. Using the display to verify pressure sensor signal voltage
The display can show the voltage level that it detects on the pressure sensor signal line by entering the password
LLRR LLRR.
The display will then scroll the text “VOLTS” and then continue to scroll the voltage detected at pin 6.
The display will continue showing the voltage until either of the magnetic switches is activated.

Table of Contents