16
Installer Setup: Deadband
Deadband
The Deadband is the number of degrees or
minutes that the thermostat waits before it
initiates the stages of heating or cooling.
1st Stage Deadband (setup step 11)
Species the temperature difference between
the room temperature and the desired setpoint
before the rst stage of heating or cooling
is allowed to turn on. (1 - 6 degrees) For
example, if the heat setpoint is 68˚ and the 1st
Stage deadband is set to 2 degrees, the room
temperature will need to reach 66˚ before the
heat turns on. For additional information on
deadband, go to page 25.
Minimum Heat/Cool
Setpoint Difference (setup step 12)
This feature allows the user to set the minimum
gap between Heat and Cool setpoints in AUTO
mode. Select from 0 to 6 degrees.