53
ifm Device Manual IO-Link Master with Modbus interface CabinetLine 8 Ports IP 20 (AL1940) 05 / 2018
Configuration Modbus
>
8.3.4 Read input data of individual IO-Link ports
23072
Register area for separate access to input data of the individual IO-Link ports: → Single Port Access
(→ p. 82)
The area contains the following data for each IO-Link port X01...X08:
Digital input data at clamp 2 / clamp 4 (DI)
Diagnostic and status information of the connected IO-Link devices
Input data IO-Link
Observe the general rules for access to the Modbus registers (→ Rules for accessing the Modbus
register (→ p. 58))!
The parameter "Invalid Data" indicates whether the read IO-Link input data is valid.
► Also read and evaluate the corresponding diagnostic information!
Port X01: Digital Input - Pin 2 / Pin 4 (DI)
Port X01: Diagnostic data
Port X01: Input Data - IO-Link (n bytes)
Port X02: Digital Input - Pin 2 / Pin 4 (DI)
Port X02: Diagnostic data
Port X02: Input Data - IO-Link (n bytes)
Port X03: Digital Input - Pin 2 / Pin 4 (DI)
Port X03: Diagnostic data
Port X03: Input Data - IO-Link (n bytes)
Port X04: Digital Input - Pin 2 / Pin 4 (DI)
Port X04: Diagnostic data
Port X04: Input Data - IO-Link (n bytes)
Port X05: Digital Input - Pin 2 / Pin 4 (DI)
Port X05: Diagnostic data
Port X05: Input Data IO-Link (n bytes)
Port X06: Digital Input - Pin 2 / Pin 4 (DI)
Port X06: Diagnostic data
Port X06: Input Data - IO-Link (n bytes)
Port X07: Digital Input - Pin 2 / Pin 4 (DI)
Port X07: Diagnostic data
Port X07: Input Data - IO-Link (n bytes)
Port X08: Digital Input - Pin 2 / Pin 4 (DI)
Port X08: Diagnostic data
Port X08: Input Data - IO-Link (n bytes)
r .. read only
n = [2,4,8,16,32]; is determined by parameters [Process Data Length] (→ Configuration Area (→ p. 73))