27
INSTALLERUSERMAINTENANCE TECHNICIAN
Error
Code
Anomaly signalled Cause Boiler status / Solution
45 High T
e boiler detects a sudden, unexpected increase in the ΔT between
the ow probe and the system return probe.
e power of the burner is limited to pre-
vent damage to the condensation module
and once the right ΔT is restored, the boiler
resumes regular operation. Make sure there
is water circulating in the boiler, that the
pump is congured according to system
requirements and that the return probe
works properly. (1) (2)
47
Burner power limi-
tation
Should ue high temperature be detected, the boiler reduces power
supplied so as not to damage it.
(1)
51
CAR Wireless commu-
nication failure
If there is no communication between the boiler and Wireless version
CAR, an anomaly is signalled. From this moment, it is only possible
to control the system by means of the control panel of the boiler itself.
Check operation of the Wireless CAR,
check the battery charge (refer to the relative
instructions booklet).
60
Anomaly pump
blocked
e pump is stopped due to one of the following causes:
Impeller blocked, electrical fault.
Try to unblock the pump as described in
the relative section. If normal conditions are
restored the boiler restarts without having
to be reset (1)
61 Air in circulator pump Air is detected inside the pump; the pump cannot work.
Vent the pump and the central heating cir-
cuit. If normal conditions are restored the
boiler restarts without having to be reset (1)
70
Return/ow probe
exchange
In case of an incorrect boiler wiring connection the error is detected e boiler does not start (1)
75
Return and/or ow
probe malfunction
Possible failure of one or both system return and ow probes e boiler does not start (1)
76
Return and/or flow
probes temperature
dri
A malfunction of one or both system return and ow probes is
detected
e boiler does not start (1)
(1) If the block or anomaly persists, contact an authorised company (e.g. Authorized Technical Aer-Sales Service).
(2) The anomaly can only be verified in the list of errors in the Information menu