I-Control manual page 10
Max.delta T. (0 to 50˚C)
If the temperature difference between the drinking water circuit and the supply circuit rises above the set delta
temperature, flushing will start automatically. Note: When no temperature sensor has been installed in the supply
circuit, this function will not be displayed and no automatic flushing will occur.
Max.flushing (1 to 100)
Flushing on a temperature basis will not exceed the set number of times per day. If more flushing is needed, there
will be an alarm.
Dirty water detection
Select this menu by pressing the key in the main screen. SelectDirty water detectand press the key.
The functions in this menu concern automatic flushing when the water becomes polluted.
Note: If automatic flushing based on pollution is not switched on, this menu will not be displayed.
Note: This menu can be reached directly from the main screen by pressing the shortcut ‘0/DSENS’.
Dirt detect (0-100%)
The I-Control indicates the degree of pollution. When exceeding a preset value, the flushing will start
automatically. Note: This function is only displayed when set in the installer’s menu.
Dirt detect (on - off)
This function is almost identical to the abovementioned; however, the installer has chosen for a an on-off pollution
sensor. When this sensor indicates that the water is polluted ('on'), flushing will take place
. Note: This function is
only displayed when an on-off pollution sensor is set in the installer’s menu.
Start flushing (1 to 100%)
If pollution exceeds a preset value, flushing will start automatically. Note: Dependent on the settings set by the
installer, this function may not be displayed.
Max.flushing (1 to 100)
When the maximal number of flushings based on pollution on the present day has been reached, flushing will stop
and an alarm will appear on the screen.
Detection time (00:00 to 23:59 minutes: hours)
This setting can be used to adjust the time for which the dirt detection should indicate that the drinking water is
contaminated before the automatic flush is started. This can be set from 0 minutes to 23 hours and 59 minutes.
When the set value is 0, the measured soil detection value is immediately adopted.
Curve
Select this menu by pressing the key in the main summary screen. SelectCurve” and press the key to
give access to the curve settings. By using this curve, it is possible to adjust the starting times and the automatic
flushing times according to the age of the birds. The day counter determines the progression of the curve.
Note: This function is only displayed when set in the installer’s menu.
Note: This menu can be reached directly from the main screen by pressing the shortcut ‘-/CURVE’ .
The curve contains 6 “breakpoints” to select different start times. This enables you to decide on which day a
specific breakpoint has to be carried out. When the day counter has reached the given breakpoint, the starting
times are carried out at the breakpoint settings. Note: Breakpoint 0 always starts on day 1, which is the beginning
of a new round. For the remaining breakpoints (1-5), you can determine the day numbers at your discretion.