EasyManuals Logo

Incon task sentinel TS-750 User Manual

Default Icon
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #170 background imageLoading...
Page #170 background image
Problem Solving Page 29 - 5
29
NOTE:
Diagnostic text
in the left column, is shown
bolded
{ become alarms if active for 48 hours }
#
Printed / Faxed / Displayed
Alarm / Warning Text:
Alarm Type:
System WARNING / Error Descriptions and
ALARM Descriptions
(actions to take)
LEAK (Continued )SYSTEM
3. Second confirming failure: Call Service
provider / local Regulatory Agency / Manager per
policy procedure at your site or 4. Second Test
passes [false leak failure]... turn pump and
dispenser power back on and restore normal
operation.
48
LEVEL ERROR / LEVEL ERR
/ LVL ERR
SYSTEM
WARNING - product Level - calculation Error
(call
service provider to fix this problem)
49
MEMORY ERROR / MEM
ERR
SYSTEM
WARNING - Memory Error (power quality problem,
or memory-backup battery is dead...
have service
provider check / replace battery and verify that
unit works correctly as originally programmed)
50
NO PROBE /
NO PROB
SYSTEM
Diagnostic WARNING - No Probe Detected
NO
PROB
(call service provider to correct this
problem)
51
PAPER OUT SYSTEM
The printer is out of paper
(add new roll of TS-TP2
thermal paper)
52
POWER DOWN SYSTEM
WARNING - Power Down (time that
the unit lost
power or was turned off
)
53
POWER UP SYSTEM
WARNING - Power Up (time that the unit was
powered up / regained power)
54
PROBE SYNC /
PRB SYC
SYSTEM
Diagnostic WARNING - signal lost from Probe
(
PRB SYC
call service provider if continuous)
55
RTC FAILURE SYSTEM
Real Time Clock has failed. Clock and Calendar
settings are affected. Verify date and time are
correct (use CHECK key). Change settings as
needed. Cycle power. Verify settings (use CHECK
key).
56
RTD TABLE ERROR / RTD
TBL ER / RTD TBL
SYSTEM
WARNING - Number of RTDs Error does not
match actual / setup - programmed value
(call
service provider to correct this problem)
57
SCALD TEST FAILED /
SCALD DETECTED LEAK
SYSTEM
WARNING - SCALD Leak Test Failed alarm report
for Tank N
(run a Standard leak test for that
tank... See LEAK)
58
SEN DAT / SENS DATA /
SENSOR DATA ERROR
SYSTEM
WARNING - a BriteSensor @ Channel #N is
sending data errors
(call service provider ASAP)
59
SENS LOSS OF SIGNAL /
SIG LOST / SEN SIG
SYSTEM
WARNING - no data sent / signal lost from
BriteSensor @ Channel #N
(call service provider
ASAP to correct this)
60
SENSOR ID ERROR /
SENSOR ID / SENS ID
SYSTEM
WARNING - a Standard sensor or BriteSensor
was incorrectly typed / identified
(call your service
provider to correct this)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Incon task sentinel TS-750 and is the answer not in the manual?

Incon task sentinel TS-750 Specifications

General IconGeneral
BrandIncon
Modeltask sentinel TS-750
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals