Leak Detection Sensors Page 17 - 3
17
T SP-ULS
T SP-HLS
TSP-HIS
T SP-EIS
TSP
-D
IS
TSP-DDS
TSP-DTS
T SP-DVS
TSP-MWS
Special Vapor Sensor Menu ( Continued... )
VAP THRSH (see TSP-DVS install manual)
SENSOR VAPOR THRESHOLD N
+2000.0
0.0 to 65535.0 (Enter vapor threshold to 1000
RVUs above normal in-well reading)
VAP OFFST (see TSP-DVS install manual)
SENSOR VAPOR OFFSET
+0
0.0 to 65535.0 (Enter vapor offset)
Leak Detection Sensors
Standard Sensors (below... all Alarms = STD N)
➀
TSP-EIS Electro-optic Interstitial (3 wire, infrared) Standard Sensor
detects liquids in spaces between the walls of DWTs
➁
TSP-HLS High product Level (2 wire, float switch) Standard Sensor used
inside of tanks as an overfill alarm detector (or in addition to the HIGH, and
HIGH HIGH probe limits)
➂
TSP-ULS Universal Liquid Sensor (2 wire, float switch) Standard Sensor
detects liquids in: spaces between the walls of DWTs or Dispenser sumps
BriteSensors & ALARMS (all 3 wire – below)
➃
TSP-DIS Discriminating Interstitial (infrared & conductivity sensor)
BriteSensor detects liquid WATER or PRODUCT in spaces between
the walls of DWTs
➄
TSP-HIS Hydrostatic Interstitial (float switches) BriteSensor detects
HIGH BRINE or LOW BRINE levels in hydrostatic reservoirs of DWTs
➅
TSP-DDS Discriminating Dispenser Sump (conductivity strip & floats)
BriteSensor detects liquid PRODUCT or WATER or SUMP FULL
in dispenser sumps
➆
TSP-DTS Discriminating Turbine Sump (conductivity strip & floats)
BriteSensor detects liquid PRODUCT or WATER or SUMP FULL in
STP containment sumps
➇
TSP-MWS Discriminating ground water monitoring well (float & conductivity
strip) BriteSensor – detects DRY WELL (no water in well) or PRODUCT
floating on ground water in monitoring wells
➈
TSP-DVS Discriminating Vapor Well (vapor & conductivity strip)
BriteSensor detects liquid WATER or product VAPOR in vapor
monitoring wells
➇
➀
➁
➂
➃
➄
➅
➆
➈