Page 4 - 2 Tank Sentinel Setup Programming Guide
Probes – PROBE DATA Menu (C
ONTINUED
...
FROM
PREVIOUS
PA GE
)
PROBE DATA N PROBE # N shown typical for any probe # 1 – # 8
TYPE Press
M2
key.
PROBE TYPE FOR PROBE N Press
UP/DOWN
▲
▼ keys to choose.
STD 101
Press
ENTER
to accept this data.
STD 107
STD 113
STD #
probe is a STANDARD probe.
: (menus differ depending on choices)
STD 149
SPEC PROBE 1 Select SPEC PROBE N (special probe) if it
SPEC PROBE 2 is not a Standard TSP-LL2 model / type of
: probe listed in this menu...see SPECIAL
SPEC PROBE 8 menu.
PRESSURE Select PRESSURE (pressure probe)
STD 29 when programming TSP-LLP or TSP-LPG
: probes. See following section on Pressure
STD 89 probes.
GRADIENT (enter the GRADIENT from the probe label)
GRADIENT FOR PROBE N
+9.03000
8 to 9.90000
(See Installation Guide or Probe label for this
data. Also see Chapter 2 of this manual
for: Probe # — Tank # assignments)
Press
ENTER
to accept this data.
NO. FLOATS
NUMBER OF FLOATS FOR PROBE Use
UP/DOWN
▲
▼ keys to choose a #.
2 FLOATS
Press
ENTER
to accept this data.
1 FLOAT
FLT TYPE
FLOAT TYPE FOR PROBE N Use
UP/DOWN
▲
▼ keys to choose a type.
GASOLINE
Press
ENTER
to accept this data.
OIL
Probe Model
#
Probe
Gradient #
Product in
Tank (Float
type)
Number of
Probe Floats
(1 or 2)
Tank 1
Tank 2
Tank 3
Tank 4
Tank 5
Tank 6
Tank 7
Tank 8