EasyManua.ls Logo

INIM PREVIDIA COMPACT - External Communicator Wiring; E-Type Output Wiring; J-Type Output Wiring

INIM PREVIDIA COMPACT
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 Installation
Fire detection and extinguishant system
3.9 Wiring the external communicators
The Previdia Compact control panels can be used to drive remote alarm or fault signalling devices
Cables:
2-wire shielded cable
Proper section (minimum 0.5mm², maximum 2.5 mm²)
Compliant with local laws and regulations in force
The “I/O” terminals on-board the control panel [A] and the outputs supervised on the loop modules can be used to
create an E-type output (output for the activation of alarm signalling on a remote signalling device, as prescribed by
standard EN54-2).
To create a J type output (output for activation of fault status signalling on a remote signalling device, as prescribed by
standard EN54-2), only the “I/O” terminals can be used on board the control unit, which can be Programmed as active in
rest condition.
EN54:
In both cases, as the external communicator, you must use a remote communication device compliant
with standard EN54-21 [B] and equipped with a supervised activation input [C], a normally closed fault
signal output [D] and a normally-open output for confirming successful communications [E]].
If the external Communicator does not have a supervised activation input, the connection to the control
panel can be carried out by means of a relay, which must be installed inside the communicator casing.
To transmit alarm events via the I/O terminals on board the control panel, you can use normal wiring for
non-polarized devices. To transmit failure events, use the following wiring diagram
:
I/Ox I/Ox
C
NONC
3K9Ohm
orange, white,
red
B
CE
D
A
470Ohm, 2W
yellow, purple,
brown
A
Relay 24V
470Ohm
yellow, purple,
brown

Related product manuals