Inner Range Inception Security Controller Installation Manual. Rev. 6.0
© 2016 - 2023. Inner Range Pty Ltd.
13 www.innerrange.com
Zone Inputs.
Eight zone inputs are provided to allow monitoring of detection devices, door reeds, etc.
The default EOL configuration is 2k2+2k2 or 2k2+6k8 (shown in the schematic diagram below).
A different configuration may be selected. Current options are:
1k+1k (Seal=1k / Alarm=2k)
6k8+3k3 (Seal=6k8 / Alarm=10k1)
4k7+4k7 or 4k7+2k2 (Seal=4k7 / Alarm=9k4 or 6k9)
10k+10k (Seal=10k / Alarm=20k)
Example: PIR movement detector.
Example: Reed Switch.
Tamper Input.
Detector terminals may be arranged
& labelled differently to this
example. Please check the
manufacturer’s documentation.
For tamper switches provided with the recommended
enclosures, select “Open Circuit Secure” in the
Controller hardware settings in the browser.
Notes:
1) ‘Normally Closed’ Contacts are
the most common.
2) Devices with different Alarm or
Tamper contact behaviour may
be accommodated with the
‘Swap Active States’ options on
the Inputs configuration page.
See ‘Troubleshooting’ in this
manual and the tooltips.