Inner Range Inception Security Controller Installation Manual. Rev. 6.0
© 2016 - 2023. Inner Range Pty Ltd.
4 www.innerrange.com
REGULATORY INFORMATION
UL294 Requirements (North America)
Wiring methods shall be in accordance with the National Electrical Code (ANSI/NFPA70), local codes, and the authorities
having jurisdiction.
The Inception Controller, remote Modules and UniBus in-cabinet expansion boards are acceptable for indoor use only and
must be installed within the protected premises.
The AC power cord must not be plugged into an outlet controlled by a switch.
If a separate power supply is utilized for ancillary power (e.g. For electric locks), the power supply must be a UL Listed
Access Control or Burglar Alarm, Low-Voltage Class 2, Power-Limited, power source capable of a minimum of 4 hours
standby power.
All cabling must be UL Listed and/or Recognized wire.
All interconnecting devices must be UL Listed.
The Inception access control system must be used with UL listed Card Readers.
The following Listed Card Readers configured for Wiegand or RS485 (OSDP) output are compatible:
- Inner Range SIFER Reader - HID iClass - HID Proximity
- Inner Range SIFER-Keypad - HID iClass SE
Automation. The Automation functionality of this product has not been evaluated by UL.
FUSES. CAUTION - FOR CONTINUED PROTECTION AGAINST THE RISK OF FIRE, REPLACE WITH ONLY THE SAME TYPE AND
RATING OF FUSE.
Refer to the ‘Additional Resources’ chapter of this manual for a list of related documentation.
ULC-S304 Requirements (Canada)
Inception Controller total static load current must not exceed 450mA. i.e. Combined current required by the Controller
and devices powered from the LAN+, READER+, V OUT & USB outputs.
UL2610 Requirements (North America)
INSTALLATION NOTES:
Loss of communication with the monitoring station shall be treated as an alarm condition by monitoring station personnel
when the burglar alarm system is in the armed state, and as a trouble condition while the system is disarmed.
Communication medium between protected property & communications service provider shall be for the exclusive use of
the protected property and is not to be shared with other communications service provider subscribers.
The number of signals in each system used for burglar-alarm signals shall be limited to 1000.
The central/proprietary/police (monitoring) station equipment shall be designed and constructed so that any critical
component can be replaced and the system restored to service within 30 minutes.
PROGRAMMING NOTES:
Message Acknowledge “Acknowledgement signal”.
The settings for User acknowledgement of alarm messages are programmed in Configuration > Users as follows:
In Terminal Profiles > Terminal Permissions, enable the System Messages/Warningsoption.
In Manage Users > Credentials, assign the appropriate ‘Terminal Profile‘ to each User who has a Security PIN.
Entry and Exit Delay: The Entry & Exit delay settings are programmed separately for each Area.
The value programmed for Entry or Exit delay must not exceed 60 seconds.