MAINTENANCE
MAINTENANCE
Routine maintenance is essential to keep the device always

5�1 Preliminary warnings
This section is dedicated to the Technical Service
Assistance. The features of the Technical Ser-
vice Assistance are described in chapter "Recipi-
ents" p.7.
For detailed information on accessories please re-
fer to the "Conguration accessories" p. 55 sec-
tion.
      -
ered by the Kyoto Protocol. Maintenance and disposal

only.
Before each cleaning and maintenance intervention:
disconnect the device from the power mains by turn-

wait for the components to cool down in order to
avoid any burns
Carrying out any technical or cleaning work before dis-
connecting the unit from the power supply is forbidden.
Make sure that there is no voltage before operating.
After completing the maintenance work, must be re-
stored the original condition.
5�2 Once-a-year operations
The once-a-year maintenance plan includes the following
operations and checks and must be carried out by the

5�2�1 Routine maintenance of the unit
Hydrauliccircuit
Check:



absence of air in the circuit (venting)
         
evaporator
the status of thermal insulation of the hydraulic pip-
ing
the glycol percentage, if any
Electric circuit
Check:
electrical supply voltage
electric draw
tightness of connections
that there is no damage or excessive wear on the
electrical cables
the seals and sealing materials have not deteriorat-
ed to such an extent that they are no longer suitable
-
pheres inside

safety devices
Mechanical checks
Check:
the tightness of the screws, the compressors and the
electrical box, the external panelling of the unit
the conditions of the structure
Poor fastenings cause abnormal noises and vibrations.
Treat any rusty parts with paints suitable to eliminate or
reduce the rust.
Cleaning
clean cosmetic covering elements
Refrigeration checks
Make sure that:
the amount of charge complies with the size of the
room in which the parts containing the refrigerant
p.20)
ventilation equipment and vents functioning properly
and not obstructed
the marking on the equipment must remain visible
and legible. Illegible markings and graphics must be
corrected
the refrigerant pipes and components are installed
in a position in which they are unlikely to be exposed
to corrosive substances unless the components are
made of inherently corrosion-resistant materials or
adequately protected against corrosion
the thermodynamic values are within the nominal pa-
rameters
Under the provisions of Directive 517/2014/EU, plants

kg of R32 gas or 2.39 kg of R410a gas) must be checked
for leaks once a year, using either direct or indirect
      
2015/2067.
The company responsible for maintenance must keep a
logbook in which the following information is recorded:
the technician who performed the maintenance or
repair,