64
TECHNICAL INFORMATION
8�1 Technical data
Models m.u.
5 7 9 12 15
Heating performances (A 7 °C BS; W 35 °C)
Maximum heat output (1) kW 6,80 8,50 13,70 18,32 22,80
Nominal heat power (1) kW 5,58 7,10 8,10 11,59 14,61
Total absorbed power (1) kW 1,31 1,64 1,79 2,35 2,95
COP (1) 4,26 4,33 4,53 4,93 4,95
SCOP (1)(2) 4,90 4,80 4,82 4,89 4,92
Energy eciency
Energy eciency class A+++
Heating performances (A-7 °C BS; W 35 °C)
Maximum heat output (3) kW 4,59 7,72 8,73 11,70 14,74
Nominal heat power (3) kW 3,76 4,32 4,86 6,93 9,03
Total absorbed power (3) kW 1,25 1,52 1,67 2,11 2,87
COP (3) 3,01 2,84 2,91 3,28 3,15
Cooling performances (A35 °C; W 18 °C)
Maximum cooling capacity (4) kW 6,00 11,01 11,27 16,74 18,56
Nominal cooling power (4) kW 4,70 7,40 8,70 12,30 15,60
Total absorbed power (4) kW 1,30 1,80 2,10 3,00 3,90
EER (4) 3,66 4,02 4,21 4,09 4,00
SEER (5) 6,80 7,30 6,90 7,05 6,62
Cooling performances (A35 °C; W 7°C)
Maximum cooling capacity (6) kW 4,11 7,56 8,11 11,79 13,34
Nominal cooling power (6) kW 3,50 5,30 6,30 8,90 11,20
Total absorbed power (6) kW 1,40 1,80 1,80 2,80 3,50
EER (6) 2,48 3,03 3,18 3,22 3,20
SEER (7) 5,78 5,80 5,45 5,50 5,12
Hydraulic data
Nominal ow rate L/min 16,0 20,4 23,2 33,2 41,9
available pressure primary circuit kPa 65,0 64,0 58,0 31,0 31,0
expansion vessel capacity L 24 24 24 24 24
Minimum system water content L 20 30 40 50 65
Refrigerant gas data
Refrigerant charge kg 1,80 1,80 1,80 3,05 3,05
Refrigerant R32
1. Water temperature in/out 30/35 °C; outdoor air temperature 7 °C; U.R. 85%
2. Value referred to the Average climate prole for supply temperature of 35 °C. Values in compliance with Regulation 811/2013.
3. Water temperature in/out 30/35 °C; outdoor air temperature -7 °C
4. Water temperature in/out 23/18 °C; outdoor air temperature 35 °C
5. (radiant application)
6. Water temperature out 12/7 °C; outdoor air temperature 35°C
7. (fancoil application)