- 103 -
Maximum frequency
Factory
default value
50.00 Hz
F0-10
Setup Range 50.00Hz to 300.00Hz
F0-11
Frequency source
upper limit
Factory
default value
0
It is used to define the source of frequency upper limit.The frequency upper
limit can be sourced from either digital setup (F0-12) or analog input channel.
When the analog input is used to set the frequency upper limit, 100% of
analog input setup is relative to F0-12.
For example, in case of torque control, the speed control is inenabled. To
avoid occurrence of broken materials, it can use the analog value to set the
frequency upper limit. When the driver runs at the frequency upper limit, the
torque control is inenabled, and the driver continues running with frequency
upper limit.
When the frequency upper limit is analog value reference, this parameter is
used as analog value offset.
Its benchmark value is F0-12. The addition of offset frequency and analog
setup value of frequency upper limit is used as the final setup value of
frequency upper limit.
Frequency lower
limit
Factory default
value
0. 00Hz
F0-14
Setup range 0.00Hz to frequency upper limit F0-12
Frequency upper
limit
Factory
default value
50.00Hz
F0-12
Setup Range
Frequency lower limit F0-11 to maximum
frequency F0-10
Frequency upper
limit offset
Factory default
value
0.00Hz
0 F0-12 setup
1 AI1
2 AI2
3 AI3
4 PULSE setup
F0-13
Setup Range
5 Communication setup