EasyManua.ls Logo

Inovance IS300T080-C - Page 152

Inovance IS300T080-C
211 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 146 -
In this way, it can prevent the automatic running of the motor under
unexpected conditions.
Frequency
detection value
(FDT level)
Factory
default value
50.00Hz
F8-19
Setup range 0.00Hz~ maximum frequency
Frequency detection
hysteresis (FDT
hysteresis)
Factory default
value
5.0%
F8-20
Setup range 0.0%~ 100.0%(FDT level)
It is used to set the detection value of output frequency and hysteresis value
upon removing of the output action.
Fig.6-12 Schematic Diagram for FDT Level
Frequency arrival
detection amplitude
Factory
default value
0.0%
F8-21
Setup range 0.00~ 100% maximum frequency
When the output frequency of the driver reaches the setup frequency value,
this function can be used to adjust the detection amplitude, as shown the
following figure.
Output Frequency
FDT1 Level
FDT1
Hysteresis
Frequency Detection Signal
Relay
Time
Time

Table of Contents

Other manuals for Inovance IS300T080-C

Related product manuals