- 80 -
Function
code
Name LED display Setup range
Minimu
m unit
Factory
default
value
Modific-
ation
descrip-t
ion
F8-13 Reverse control Reverse control
0: Reverse rotation
enabled
1: Reverse rotation
inenabled
1 0
F8-14
Set up frequency
lower than
frequency lower
limit action
Frequency lower
limit action
0: Run with
frequency lower limit
1: Stop
2: Zero speed
operation
1 0
F8-15 Droop control Droop control 0.00Hz10.00Hz 0.01Hz 0.00Hz
F8-16
Over modulation
enabled
Over modulation
enabled
0: Over modulation
inenabled
1: Over modulation
enabled
1 1
F8-17
Setup running
time
Setup running
time
0h65535h 1h 65535h
F8-18
Start protection
selection
Start protection
selection
0: No protection
1: Protection
1 0
F8-19
Frequency
detection value
(FDTlevel)
FDT level
0.00 ~ maximum
frequency
0.01Hz 50.00Hz
F8-20
Frequency
detection
hysteresis (FDT-
hysteresis)
FDT hysteresis
0.0% ~ 100.0%(FDT
level)
0.1% 5.0%
F8-21
Frequency arrival
detection width
Frequency
arrival width
0.0 ~ 100.0%
(maximum
frequency)
0.1% 0.0%
F8-22
Earth short circuit
protection
detection upon
power-on
Earth short
circuit protection
detection upon
power-on
0: Inenabled
1: Enabled
1 1