5 Parameter Table
- 27 -
Para� No� Para� Name Setting Range Unit Default Property
A4-25 Increase of pressure loop max�
Output
0 to 50�0 0�1s 2� 0
☆
A4-26 Pressure control PID switching mode
selection
0: original algorithm
1: algorithm 1
2: algorithm 2
3: algorithm 3
1 3
★
A4-33 Integral factor 1 of algorithm 3 0 to 1�00 0�01 0�08
☆
A4-34 Integral factor 2 of algorithm 3 0 to 1�00 0�01 0�08
☆
A4-35 Integral factor 3 of algorithm 3 0 to 1�00 0�01 0�08
☆
A4-36 Integral factor 4 of algorithm 3 0 to 1�00 0�01 0�08
☆
Group F0: Basic Control
F0-00 G/p selection 1: g
2: p
1 1 ●
F0-01 Control mode 0: SVC
1: Closed loop vector control
2: V/F
1 1
★
F0-02 Command source selection 0: keypad
1: terminals
2: communication
1 0
☆
F0-03 Main frequency source x selection 0: Digital setting (non-retentive at power down)
1: Digital setting (retentive at power down)
2: AI1
3: AI2
4: AI3
5 to 8: reserved
9: communication
1 0
★
F0-08 Preset frequency 0�00 to F0-10 0�01 Hz 50�00 Hz
☆
F0-09 Running direction 0: same
1: reverse
1 0
★
F0-10 Max� frequency 50�00 to 300�00 Hz 0�01 Hz 200�00 Hz
★
F0-11 Frequency upper limit source 0: F0-12
1: AI1
2: AI2
3: AI3
4: reserve
5: communication
1 0
★
F0-12 Frequency upper limit F0-14 to F0-10 Hz 200�00
☆
F0-13 Frequency upper limit offset 0�00 to F0-10 Hz 0�00
☆
F0-14 Frequency lower limit 0�00 to F0-12 Hz 0�00
☆
F0-15 Carrier frequency 1 to 8�0 kHz Model
dependent
☆
F0-16 Carrier frequency auto adjusting
selection
0: Disable
1: enable
1 1
☆
F0-17 Acceleration time 1 0�0s to 6500�0s 0�1s 20�0s
☆
F0-18 Deceleration time 1 0�0s to 6500�0s 0�1s 20�0s
☆