3 Easy Setup
- 21 -
Para� No� Para� Name Setting Range Unit Default Commission
F5-17 FMR output delay time 0�0 to 3600�0 s 0�0
F5-18 Relay 1 output delay
time
0�0 to 3600�0 s 0�0
F5-19 Relay 2 output delay
time
0�0 to 3600�0 s 0�0
F5-20 DO1 output delay time 0�0 to 3600�0 s 0�0
F5-21 DO2 output delay time 0�0 to 3600�0 s 0�0
F5-22 DO active mode
selection
0: Positive logic
1: Negative logic
DO2 active mode
DO1 active mode
Relay 2 active mode
Relay 1 active mode
FMR active mode
N�A� 00000
Note
Positive logic means that, DO output terminal is normally the default state�
Negative logic means the opposite situation�
Step 10: Set Startup Frequency If Needed
Para� No� Para� Name Setting Range Unit Default Commission
F6-03 Startup frequency 0�00 to 10�00 Hz 0�00
F6-04 Startup frequency active
time
0�0 to 100�0 s 0�0
Step 11: Set S-Curve If Needed
Para� No� Para� Name Setting Range Unit Default Commission
F6-07 Acceleration/
Deceleration mode
0: Linear mode
1: S-curve mode A
2: S-curve mode B
N�A� 0 1
F6-08 Time proportion of
S-curve start segment
0�0 to [100�0 minus F6-09] % 30�0
F6-09 Time proportion of
S-curve end segment
0�0 to [100�0 minus F6-08] % 30�0