3 Easy Setup
- 17 -
Step 6: Select Operation Mode
Para� No� Para� Name Setting Range Unit Default Commission
F0-02 Command source
selection
0: Keypad control
1: Terminal control
2: Communication control
N�A� 0
F4-11 Terminal command
mode
0: Two-wire control mode 1
1: Two-wire control mode 2
2: Three-wire control mode 1
3: Three-wire control mode 2
N�A� 0
F0-
02
Command source selection
Serial
communication
Terminal
I/O control
DI
AI1
Operating panel
(keypad & display)
F
4-11
Terminal command mode
DI
FWD
REV
DI
COM
Two-wire
control mode 1
Two-wire
control mode 2
DI
Run enabled
Direction
DI
COM
DI
FWD
Stop
DI
COM
REV
DI
DI
Run enabled
Stop
DI
COM
Direction
DI
Three-wire
control mode 1
Three-wire
control mode 2

Table of Contents