3 Easy Setup
- 18 -
Step 7: Set Start Mode And Stop Mode
Para� No� Para� Name Setting Range Unit Default Commission
F6-00 Start mode 0: Direct startup
1: Reserved
2: Pre-excited startup
N�A� 0
F6-10 Stop mode 0: Decelerate to stop
1: Coast to stop
N�A� 0
Step 8: Set Acceleration And Deceleration Parameters
Para� No� Para� Name Setting Range Unit Default Commission
F0-17 Acceleration time 1 0�00 to 650�00 (if F0-19 = 2)
0�0 to 6500�0 (if F0-19 = 1)
0 to 65000 (if F0-19 = 0)
s Model
dependent
F0-18 Deceleration time 1 0�00 to 650�00 (if F0-19 = 2)
0�0 to 6500�0 (if F0-19 = 1)
0 to 65000 (if F0-19 = 0)
s Model
dependent
F0-19 Acceleration/
Deceleration time unit
0: 1s
1: 0�1s
2: 0�01s
N�A� 1
F6-07 Acceleration/
Deceleration mode
0: Linear mode
1: S-curve mode A
2: S-curve mode B
N�A� 0
Step 9: Set DI And DO If Needed
DI Setting
Para� No� Para� Name Setting Range Unit Default Commission
F4-00 DI1 function selection 0: No function
1: Forward RUN (FWD)
2: Reverse RUN (REV)
3: Three-wire control
4: Forward JOG (FJOG)
5: Reverse JOG (RJOG)
6: Terminal UP
7: Terminal DOWN
8: Coast to stop
9: Fault reset (RESET)
10: RUN pause
11: External fault normally open (NO) input
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
15: Multi-reference terminal 4
16: Terminal 1 for acceleration/deceleration
time selection
17: Terminal 2 for acceleration/deceleration
time selection
18: Frequency source switchover
19: UP and DOWN setting clear (terminal,
keypad)
20: Command source switchover terminal 1
21: Acceleration/Deceleration prohibited
N�A� 1
FWD
F4-01 DI2 function selection N�A� 4
FJOG
F4-02 DI3 function selection N�A� 9
RESET