3 Easy Setup
- 20 -
DO Setting
Para� No� Para� Name Setting Range Unit Default Commission
F5-00 FM terminal output
mode
0: Pulse output (FMP)
1: Switch signal output (FMR)
N�A� 0
F5-01 FMR function
(open-collector output
terminal) selection
0: No output
1: AC drive running
2: Fault output
3: Frequency-level detection FDT1 output
4: Frequency reached
5: Zero-speed running (no output at stop)
6: Motor overload pre-warning
7: AC drive overload pre-warning
8: Set count value reached
9: Designated count value reached
10: Length reached
11: PLC cycle completed
12: Accumulative running time reached
13: Frequency limited
14: Torque limited
15: Ready for RUN
16: Reserved
17: Frequency upper limit reached
18: Frequency lower limit reached (no output
at stop)
19: Undervoltage state output
20: Communication setting
21: Reserved
22: Reserved
23: Zero-speed running 2 (having output at
stop)
24: Accumulative power-on time reached
25: Frequency level detection FDT2 output
26: Frequency 1 reached
27: Frequency 2 reached
28: Current 1 reached
29: Current 2 reached
30: Timing duration reached
31: AI1 input limit exceeded
32: Load lost
33: Reverse running
34: Zero current state
35: Module temperature reached
36: Output current limit exceeded
37: Frequency lower limit reached (having
output at stop)
38: Alarm output
39: Reserved
40: Current running time reached
41: Fault output (no output at undervoltage)
N�A� 0
No output
F5-02 Relay function
(T/A-T/B-T/C) selection
N�A� 2
Fault output
F5-03 Extension card relay
function (P/A-P/B-P/C)
selection
N�A� 0
No output
F5-04 DO1 function selection
(open-collector output
terminal)
N�A� 1
AC drive
running
F5-05 Extension card DO2
function selection
N�A� 4
Frequency
reached