5 Parameter Table
- 36 -
Para� No� Para� Name Setting Range Unit Default Commission
F8-28 Frequency detection value
(FDT2)
0�00 to max frequency N�A� 50�00
F8-29 Frequency detection
hysteresis (FDT2 hysteresis)
0�0 to 100�0 (FDT2 level) % 5�0
F8-30 Detection value 1 of any
frequency reaching
0�00 to max frequency Hz 50�00
F8-31 Detection amplitude 1 of any
frequency reaching
0�0 to 100�0 (max frequency) % 0�0
F8-32 Detection value 2 of any
frequency reaching
0�00 to max frequency Hz 50�00
F8-33 Detection amplitude 2 of any
frequency reaching
0�0 to 100�0 (max frequency) % 0�0
F8-34 Zero current detection level 0�0 to 300�0 (rated motor current as 100%) % 5�0
F8-35 Zero current detection delay 0�01 to 600�00 s 0�10
F8-36 Output overcurrent threshold 0�0 (no detection)
0�1 to 300�0 (rated motor current)
% 200�0
F8-37 Output overcurrent detection
delay
0�00 to 600�00 s 0�00
F8-38 Detection value 1 of any
current reached
0�0 to 300�0 (rated motor current) % 100�0
F8-39 Detection amplitude 1 of any
current reached
0�0 to 300�0 (rated motor current) % 0�0
F8-40 Detection value 2 of any
current reached
0�0 to 300�0 (rated motor current) % 100�0
F8-41 Detection amplitude 2 of any
current reached
0�0 to 300�0 (rated motor current) % 0�0
F8-42 Timing function 0: Disabled
1: Enabled
N�A� 0
F8-43 Timing duration source 0 to 3 N�A� 0
F8-44 Timing duration 0�0 to 6500�0 min 0�0
F8-45 AI1 input voltage lower limit 0 to F8-46 V 3�10
F8-46 AI1 input voltage upper limit F8-45 to 11�00 V 6�80
F8-47 Module temperature
threshold
0 to 100 °C 75
F8-48 Cooling fan working mode 0: Fan working during running
1: Fan working continuously
N�A� 0
F8-49 Wakeup frequency Dormant frequency (F8-51) to max
frequency (F0-10)
Hz 0�00
F8-50 Wakeup delay 0�0 to 6500�0 s 0�0
F8-51 Hibernating frequency 0�00 to wakeup frequency (F8-49) Hz 0�00
F8-52 Hibernating delay 0�0 to 6500�0 s 0�0
F8-53 Current running time reached 0�0 to 6500�0 min 0�0
F8-54 Output power correction
coefcient
0�0 to 200�0 % 100�0
F8-55 Deceleration time for
emergency stop
0�00 to 650�00 (F0-19 = 2)
0�0 to 6500�0 (F0-19 = 1)
0 to 65000 (F0-19 = 0)
s 0�1