5 Parameter Table
- 38 -
Para� No� Para� Name Setting Range Unit Default Commission
F9-38 Output terminal status upon
1st fault
N�A� N�A� N�A�
F9-39 Frequency upon 1st fault N�A� N�A� N�A�
F9-40 Current upon 1st fault N�A� N�A� N�A�
F9-41 Bus voltage upon 3rd fault N�A� N�A� N�A�
F9-42 Input terminal status upon
1st fault
N�A� N�A� N�A�
F9-43 Output terminal status upon
1st fault
N�A� N�A� N�A�
F9-44 Frequency upon 1st fault N�A� N�A� N�A�
F9-47 Fault protection action
selection 1
00000 to 22222 N�A� 0000
F9-48 Fault protection action
selection 2
00000 to 21111 N�A� 0000
F9-49 Fault protection action
selection 3
00000 to 22222 N�A� 0000
F9-54 Frequency selection for
continuing to run upon fault
0 to 4 N�A� 0
F9-55 Backup frequency upon
abnormality
0�0 to 100�0 (max frequency) Hz 100�0
F9-59 Action selection at
instantaneous power failure
0: Invalid
1: Decelerate
2: Decelerate to stop
N�A� 0
F9-60 Pause judging voltage at
instantaneous power failure
80 to 100 % 85
F9-61 Voltage recovery judging
time at instantaneous power
failure
0�0 to 100�0 s 0�5
F9-62 Judging voltage at
instantaneous power failure
60 to F9-60 (standard bus voltage) % 80
F9-63 Protection upon load lost 0: Disabled
1: Enabled
N�A� 0
F9-64 Load lost detection level 0�0 to 100�0 % 10�0
F9-65 Load lost detection time 0�0 to 60�0 s 1�0
F9-66 Min� PID error 2 0�0 to 100�0 % 0�0
F9-69 Overspeed detection level 0�0 to 50�0 (max� output frequency) % 20�0
F9-70 Overspeed detection time 0�0: No detection
0�1 to 60�0
s 0�0
F9-71 Power dip ride-through gain
Kp
0 to 100 N�A� 40
F9-72 Power dip ride-through
integral coefcient
0 to 100 N�A� 30
F9-73 Deceleration time of power
dip ride-through
0�0 to 300�0 s 20�0