23
5 Function code table
NOTE: not all parameters are listed, here below are relevant to open loop elevator applications.
5.1 Group F0: fundamental
Function
Code
Parameter name Setting Range
Commission
F0-01 Motor 1 control mode 0 : Sensor-less flux vector control (SFVC)
2 : V/F control
N.A
2
F0-02 Command source selection 0 : Operation panel control (LED off)
1 : Terminal control (LED on)
2 : Communication control (LED flashing)
N.A
1
F0-03 Main frequency source X
selection
2 : AI-1
3 : AI-2
4 : AI-3
6 : Multi-reference
N.A
6
F0-07 Frequency source selection 0 : Main frequency source X
0
F0-09 Rotation direction 0: Same direction
1: Reverse direction
N.A
0
F0-10 Maximum frequency 50.00 to 100.00
F0-15 Carrier frequency 0.5 to 11.0
(SVC mode: 0.5 to 9)
(VF mode: 0.5 to 11)
kHz
F0-17 Acceleration time 1 0.00 to 650.00 (F0-19 = 2)
0.0 to 6500.0 (F0-19 = 1)
0 to 65000 (F0-19 = 0)
Sec
3.0
F0-18 Deceleration time 1 0.00 to 650.00 (F0-19 = 2)
0.0 to 6500.0 (F0-19 = 1)
0 to 65000 (F0-19 = 0)
Sec
Acceleration/Deceleration time
unit
0 : 1
1 : 0.1
2 : 0.01
Sec