30 
 
5.7 Group F6: start and stop control  
Function  
Code 
Parameter name Setting Range 
Commission 
F6-00 Start mode 0 : Direct start  
1 : Rotational speed tracking restart 
2 : Pre-excited start (asynchronous motor) 
N.A
0  
F6-03 Startup frequency 0.0 to 10.0 
1.0  
F6-04 Startup frequency 
0.3  
F6-05 DC injection 1 level 0 to 150 %
injection 1 active set time
0  
F6-07 Acceleration/Deceleration 
mode 
0 : Linear acceleration/ deceleration 
3:  S-curve acceleration/ deceleration C 
N.A
3  
F6-08 Time proportion of S-curve 
Accel start 
0.0% to Min[(100.0% - F6-09), 80%] 
%
80.0  
F6-09 Time proportion of S-curve 
Accel end 
0.0% to Min[(100.0% - F6-08), 80%] 
%
10.0  
F6-10 Stop mode 0 : Decelerate to stop 
1 : Coast to stop 
N.A
0  
F6-11 DC injection 2 frequency 
threshold 
0.00 Hz to maximum frequency 
Hz
0.50  
F6-12 DC Injection 2 delay ON 
0.0  
F6-13 DC injection 2 level 0 to 150 %
injection 2 active set  time
0.5  
F6-26 Time proportion of S-curve 
Decel start  
0.0% to Min[(100.0% - F6-27), 80%] 
%
20.0  
F6-27 Time proportion of S-curve 
Decel end  
0.0% to Min[(100.0% - F6-26), 80%] 
%
30.0  
 
5.8 Group F7: product and software version checking  
Function  
Code 
Parameter name Setting Range 
Commission 
F7-08 Product number N.A. 
display 
F7-10 Performance software 
version 
N.A. 
312.xx display 
F7-11 Functional software version
display 
F7-15 Performance software 
temporary version 
N.A. 
0.00 display 
F7-16 Functional software 
temporary version 
N.A.