EasyManua.ls Logo

Inovance MD380L - Control Board Terminal Description; Extension I;O Card MD38101 Details

Inovance MD380L
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Terminals of main control board
Terminal Terminal Name Description
+10V-GND
+10 VDC power supply
Provide +10 VDC power supply externally. Usually, it provides power
supply to the external potentiometer with resistance range of 1 to
Max. output current: 10 mA.
+24V-COM +24 VDC power supply
Provide +24 VDC power supply externally. Usually, it provides power
supply to DI/DO terminals and external sensors.
Max. output current: 200 mA.
OP Input terminal of external power supply
Connect to +24 VDC by default.
Whether it connects to +24 V or COM is
decided by jumper J7.
When DI1 to DI5 need to be driven by the external
signal, OP needs to be connected to the external power supply and be
disconnected from +24 VDC.
AI1-GND Analog input 1
AI1 input voltage range: 0 to 10 VDC.
Impedance: 22
AI2-GND Analog input 2
AI2 can be used as voltage input or current input, which is chosen by
jumper J8 on main control card.
Input range: 0 to 10 VDC or 4 to 20 mA.
Impedance: 22 if voltage input, 500 if current input.
DI1-COM Digital input 1
Optical coupling isolation, compatible with dual-polarity input.
Input voltage range: 9 to 30 VDC.
DI2-COM Digital input 2
DI3-COM Digital input 3
DI4-COM Digital input 4
DI5-COM High-speed pulse input
Besides features of DI1 to DI4, it can be used for high-
speed pulse input.
Max. input frequency: 100 kHz.
AO1-GND Analog output 1
Voltage or current output, determined by jumper J5 on main control
board
.
Output voltage range: 0 to 10 VDC.
Output current range: 0 to 20 mA.
DO1-CME Digital output 1
Open-collector, dual polarity output, optical coupling isolated.
Voltage range: 0 to 24 VDC.
Current range: 0 to 50 mA.
FM-COM High-speed pulse output
I
t is restricted by F5-00 (FM terminal output mode selection).
As a high-speed pulse output, the maximum frequency is 100 kHz.
As an open-collector output, its specification is the same as that of DO1
Voltage range: 0 to 24 VDC.
Current range: 0 to 50 mA.
T/A-T/B Normally closed terminal Contact driving capacity:
250 VAC, 3 A; 30 VDC, 1 A.
T/A-T/C Normally open terminal