Structure Model
RST/UVW
Ground Cable
Screw
Cable Size
(mm
2
)
<1>
Cable Lug
Cable Size
(mm
2
)
<1>
Cable Lug
T10 MD520‑2T90(S) 2 x (3 x 120) BC120‑12 120 BC120‑12 M12
MD520‑2T110(S) 2 x (3 x 150) BC150‑12 150 BC150‑12 M12
T11 MD520‑2T132(S) 2 x (3 x 185) BC185‑16 185 BC185‑16 M16
T12 MD520‑2T160(S) 2 x (3 x 240) BC240‑16 240 BC240‑16 M16
MD520‑2T200(S) 2 x (3 x 240) BC240‑16 240 BC240‑16 M16
Table 2–4 Cable selection (single‑phase 200 V to 240 V)
Structure Model
RST/UVW
Ground Cable
Screw
Cable Size
(mm
2
)
<1>
Cable Lug
Cable Size
(mm
2
)
<1>
Cable Lug
T2 MD520‑2S0.4B(S)
0.75 TNR0.75‑4 0.75 TNR8‑5
M4
MD520‑2S0.7B(S)
1.5 TNR0.75‑4 1.5 TNR8‑5
MD520‑2S1.5B(S)
2.5 TNR1.25‑4 1.5 TNR8‑5
MD520‑2S2.2B(S)
4 TNR2‑4 2.5 TNR8‑5
Table 2–5 Cable selection (single‑phase 200 V to 240 V) (UL certified)
Structure Model
RST/UVW
Ground Cable
Screw
Cable Size
(AWG)
Cable Lug
Cable Size
(AWG)
Cable Lug
T2 MD520‑2S0.4 B(S)
14 TLK2.5‑4 2 x 14 TLK2.5‑4
M4
MD520‑2S0.7 B(S)
14 TLK2.5‑4 2 x 14 TLK2.5‑4
MD520‑2S1.5 B(S)
14 TLK2.5‑4 2 x 14 TLK2.5‑4
MD520‑2S2.2 B(S)
10 TLK6‑4 2 × 10 TLK6‑4
<1>: Chinese standards applicable; 3 x 10: one 3‑core cable; 2 x (3 x 95): two 3‑core
cables; <2>: American standards applicable; 5: 5AWG; 1/0: 0AWG; 2/0: 00AWG; 3/0:
000AWG; 4/0: 0000AWG; 2 x 250: two 250 kcmil cables.
Recommended lugs
The following recommended lugs are the TNR, GTNR, and BC series of Suzhou Yuanli.
UL‑certified lugs are the TLK and SQNBS series of KST.