Installation
‑41‑
Figure 5‑2 Installing multiple AC drives (T1 to T9 models) side by side
Table 5–3 Installation clearance
Power Rating
Clearance (mm)
0.4 kW to 15 kW A1 10
18.5 kW to 22 kW A1 10
30 kW to 37 kW A1 50
45 kW to 160 kW A1 50
Installing one above another
Where an AC drive needs to be installed above another, the heat generated by the
lower AC drive may act on the upper one, causing over‑temperature or overload of
the upper one. In this case, install an air guide plate, as shown in "
Figure 5–3
Installing one above another
"
on page 42
.