Wiring
‑79‑
EMC requirements
1. To avoid short circuit between adjacent conductors, use shielded cables and
connect the shield to the protective bonding circuit. Alternatively, use flat cables
and connect a grounding wire between adjacent signal conductors.
2. Double‑shielded or single‑shielded twisted multi‑pair cable is recommended.
3. Fix and ground the cable shield using a piece of conductive metal.
Figure 6‑2 Cable clamp
4. The maximum allowable cable length between the AC drive and the activation
switch is 30 m.