5.1.5  Verify that the following voltage levels are OK and within the limit 
  240VAC Level 
  ± 24VDC Level 
  110VAC Level 
  ±110VDC Level (If present) 
 
5.1.6  After confirming the correct voltage level, switch OFF the Control Panel Circuit Breakers  
   
      
 
 
5.1.7  Connect the Control terminal wiring on MCTC-MCB-G of NICE 1000 
 
     
 
  Connected the Safety circuit wiring to the field as per the Electrical drawing. Safety circuit terminal 
starts from 101 and ends at 132 terminal  
 
  Connected the wiring for Up/Down terminal floor Limit and slowdown switches 
 
  The distance for  terminal floor slowdown should be 1300mm~L/2 from the floor level and the distance for 
terminal floor direction limit switches should be 30 to40 mm above the floor level in top terminal/ below the 
floor level in bottom terminal            
LTerminal floor height  
 
  For terminal slowdown, it can be calculated as follow  
Slowdown distance (S) > (F0-04 * F0-04) / (2 * F3-08) 
(Default: S=1500mm for 1mps)