6.3 Normal operation & its signal verification
Once the Door commissioning is completed, the lift is ready for normal operation
Turn ON the Inspection button into Normal mode
Input signal status of Main Control Board (MCB) while the lift at top terminal floor level with doors are
closed in normal mode
Running Contactor
Feedback (SW)
Brake Contactor Feedback
(BY)
Inspection mode input signal
OFFINS mode
ON Normal Mode
Inspection mode UP signal
For UP direction command in INS
mode
Inspection mode DOWN
signal
For DOWN direction command in
INS mode
UP direction limit signal
Down direction limit signal
Up terminal slowdown
signal
As the Lift car is located at Top
Most Floor where the UP
terminal slowdown got activated
Down terminal slowdown
signal
Over Load Feedback Signal
If Load cell is not available, keep
F5-13=0
Door Open Limit feedback
signal
If DO limit signal is ‘NC’
contact, keep F5-14=122
If Door IR sensor feedback is
‘NO’, keep F5-15=26
Door Close Limit Feedback
signal
If DC limit signal is ‘NC’
contact, keep F5-14=124
Shorting Contactor
Feedback (FX)
Manual Door R/C contactor
Feedback
Applicable for Manual Door
only
Applicable for UPS ready ARD
function
Safety Circuit feedback
signal
If all the field safety circuits are
ok, then the X25 LED gets ON
Door lock safety circuit
feedback signal 1
If Car Door is safely closed, then
X26 LED gets ON
Door lock safety circuit
feedback signal 1
If All landing doors are safely
closed, then X26 LED gets ON