6.2.2 For Manual Door Setup Procedure
Please refer NICE1000 Manual door ver2.0 Electrical Drawing and NICE100 User Manual
Verify the software version for NICE1000 Integrated controller. The suitable software version is
given in the below table
Enable the bit11 of FE-14 for manual door Function as follow
Select and Press enter; now the display will show
The first two digits represent the bit number and the last single digit to enable or disable the
corresponding selected bit number.
Using UP/DOWN key on the keypad, select bit3 & Enable the bit
DRC contactor NC feedback enable function setting
DRC contactor Function enable setting
Disabling the auto door DO function
Disabling the auto door DC function
Disabling the auto door open limit function
Disabling the auto door sensor function
Disabling the auto door Close limit function
Retiring Cam enable duration to verify landing door
safety contact
Retiring Cam disable duration to verify the landing door
safety contact
Adjust FB-03=5(Default) to modify Floor waiting time to attend the next registered call
Door open Buzzer output terminal is Y21 in the Main Control Board (MCB)
If the landing door is kept open after usage, NICE1000 tries for three times by giving the output to
the DRC contactor until the landing door safety contact is closed (landing door close). During this
period NICE1000 also gives door open buzzer output at Y21 terminal. If the landing door is not
closed within the three time try, NICE1000 cancels all registered calls and goes to idle mode.
NOTE:
For earlier software version used (FA-04=30169), to enable manual door function, please enable
bit 03 in FE-14.
Software versions prior to this (Ex. FA-04=30168, 30167) does not have manual door feature.