Version : 1.4
Date of issue : 03-07-14
For Binary functional output, set the following parameter
FE-12=3, F7-10=10, F7-11=11, F7-12=12 & F7-13=13
Binary display output terminals
Bit0Y10
Bit1Y11
Bit2Y12
Bit3Y13
8. ARD function using UPS ready:-
Confirm the ARD functional wiring is done as per the NICE1000 Electrical drawing to
connect the Suitable rated UPS to the controller
Set the following parameter to enable the ARD function
UPC contactor feedback function
UPC contactor enable function
during power failure
UPC contactor used to connect
the single phase UPS power
supply to the Controller
220VAC UPS function enable
Lesser speed will give Err30
Higher speed will drain UPS
quickly
Bit 0=1 to enable the Auto Light
Load direction selection in UPS
mode running
Add ‘1’ with the default value
in FB-07 parameter
UPS Rating Selection for suitable Motor rating
Given UPS rating is for reference
and Selection of UPS rating must
be considered with the other
control panel and field equipment