If the Input Signal sequences are ok as per the requirement, then the lift can be run in normal speed.
Select the Normal running speed using the parameter F0-03
During Normal Operation, if Error53 comes, it is due to the improper door drive close and open limit
feedback and also due to presence of landing door and car door safety by-pass
6.4 Floor Level Adjustment
For Floor Level Adjustment, Confirm that the Floor level/Door zone cutting cam/magnet centre
is matched with the centre of the switch when the lift is in exact floor level.
Cutting Fin/Cam type Pencil type Switch with
Door Zone Switch Magnet strip
Maintain the same gap between Cutting Cam to Reed switch/ Magnet strip to Reed switch in every
floor
For further adjustment, use the F4-00 = 30(default). Increase this value bit by bit if the lift car stops
before the floor level and vice versa.
For example, lift car stops 10mm above the floor level in the landing while comes from bottom floor to
this floor, then reduce the F4-00 = 20 (30-10)
6.5 Car & Landing Calls configuration:
All Car and Landing calls can be given to the L1~L20 terminal in Main Control Board (MCB) of
NICE1000
Call Function input terminal L1~L20 of MCB can be programmed in F6-11~F6-30 using Keypad
In NICE1000, Car functions are programmable and the default NICE1000 unit is programmed for 5
floor full collective function
For better understanding, Two different configurations are given below