Preparation Before Installation
‑14‑
3 Preparation Before Installation
3.1 Installation Environment
Table 3–1 Environment requirements
Item
Requirement
Installation
location
Indoors
Grid
overvoltage
Overvoltage Class III (OVC III).
Altitude
The maximum altitude is 2000 m.
● For altitudes not higher than 1000 m, derating is not required.
● Derating is required for altitudes above 1000 m (derate 1% for
every additional 100 m).
● For altitudes above 2000 m, contact Inovance.
Temperature
● Mounting/Operating temperature: 0℃ to 55℃ For temperatures
between 0℃ to 45℃, derating is not required. For temperatures
above 45℃, derate 2% for every additional 1℃.
● Storage/Transportation temperature: ‑20℃ to +70℃.
● To improve the reliability of the machine, use the servo drive in
environments without dramatic temperature change.
● When installing the servo drive into an enclosed environment such
as a control cabinet, use a cooling fan or air conditioner to keep the
temperature of the inlet air below 45℃. Failure to comply will
result in overheat or fire.
● Install the servo drive on the surface of an incombustible object
and leave sufficient surrounding space for heat dissipation.
● Take measures to prevent the servo drive from being frozen.
Ambient
humidity
Below 90% RH (no condensation)
Storage
humidity
Below 90% RH (no condensation)
Vibration
Below 4.9m/s
2
● During transportation with packing box: compliant with EN 60721‑
3‑2 Class 2M3.
● During installation without packing box: compliant with ISTA 1H.
Shock
Below 19.6m/s
2