Electrical Design Guide
‑35‑
be properly connected to systems (machines or devices), with spraying protection
applied at the installation part and the conductive metal kept in full contact.
Figure 2‑10 Cable layout
Wiring requirements
● Terminals P⊕, C, and NΘ are used to connect optional parts. Do not connect these
terminals to an AC power supply.
● To protect the main circuit, separate and cover the surface that may come into
contact with the main circuit.
● Do not allow unwanted objects to enter the wiring part of the terminal block.
● Do not solder the twisted conductors.
● The tightening torque may vary with terminals. Tighten terminal screws with the
specified tightening torque. You can use a torque screwdriver, torque ratchet, or
torque wrench to tighten terminal screws.
● When using an electric screwdriver to tighten terminal screws, set the electric
screwdriver to low speed to prevent damage to the terminal screws.
● Tighten the terminal screws with an angle not higher than 5°. Failure to comply
may damage the terminal screws.
2.5.3 Grounding and Wiring
Observe the following requirements to ensure a proper grounding of the servo drive.