3.12.2. Silent alarm and alarm time delay
Notes:
The silent alarm function and the corresponding output signal are only active
when the function has been activated.
The silent alarm is triggered by entering the opening code, whereby the last
digit has to be increased by one.
Example: 0 123456 Normal opening code
0 123457 Triggering of the silent alarm (9+1 -> 0)
After a silent alarm has been triggered, a programmed alarm time delay
becomes active. The release time of the alarm time delay is permanently set
to 5 minutes.
The alarm signal can either be signaled and connected via the EloXT
expansion unit (relay output) or via the adapter p.c.b. EloAdapt (open
collector output).
The triggering of a silent alarm is also saved in the event log.
The silent alarm and alarm time delay functions can also be programmed with
the PC software CombiComm.
Activation of the “silent alarm”
*9*
Enter program number 9
123456 *
1
Enter the master code
02*
Enter the user function number (e.g. 02)
01*
1
Enter the opening delay in the case of an alarm
in minutes, e.g. 01 minute.