FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 9
3 TECHNICAL SPECIFICATIONS
3.1 General specifications
Loop capacity:
• Every loop PCB (LC2002) can be configured as two class A loops or four class B
loops. (Except FP1200-00 2A/4B or 4A/4B; FP1200-01 2A/2B; FP1200-02 2A/2B)
• Addressable devices per loop: 126 (900 Series) or 128 (2000 Series)
• Maximum 1008 (900 Series) or 1024 (2000 Series) addressable devices per panel
• Maximum eight loops per panel (FP2000 range only)
• Loop overload: >500 mA
•
Loop operating load: 100 mA maximum
Zone capacity:
•
16 or 64 zones (expandable to 32/128, 48/192 or 64/255 zones in cabinet size B)
•
112 zones for control purposes
LCD screen:
•
Backlit alphanumeric 8 x 40 character LCD
Indicators:
• General indicators
Fire - 2 x LED - Red
Fault - 1 x LED - Amber
Disable - 1 x LED - Amber
Supply fault - 1 x LED - Amber
System fault - 1 x LED - Amber
Processor running - 1 x LED - Green
Supply On - 1 x LED - Green
• Control indicators
Silence buzzer - 1 x LED - Amber
Disable - 1 x LED - Amber
Test - 1 x LED - Amber
Third source test - 1 x LED - Amber
• Sounders indicators
Sound - 1 x LED - Red
Delay On - 1 x LED - Amber
Delay Off - 1 x LED - Amber
Fault/Disable - 1 x LED - Amber
Silence - 1 x LED - Amber