FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 11
Tamper switch (FP2000 Range only):
Fitted to the inside of the fire panel door to record any entry to the cabinet.
Third source (when implemented on the FP2000 range only):
Test button and LED to test total loss of power supply.
Communication ports:
2 x DB-9 serial port (set-up, upload/download, internal printer (where applicable),
graphics, remote operation/graphic package)
1 x current loop (to connect repeaters and fireman’s panels)
Current Loop:
Maximum 15 devices
Maximum 1 km between 2 current loop devices
Aritech FM800 / FR800 - German fire brigade panel (according to DIN 14661) can be
connected.
Cable capacitance max. 150 nF
3.2 Panel specifications
3.2.1 Standard Outputs
Standard Outputs
(All standard outputs are
located on the sounder
board.)
FP/FR1xxx & FR2000
(
FP1100 and FP1216 only;
FP1200 optional – SD1200
board used)
FP1216EN & FP1264
(SD2000 board)
FP/FR2xxx
(FP2xxx only -
SD2000 board used)
OUT 1:
Output to alarm devices
(Sounders)
A: 24 V – 100 mA supervised*
(Supervision at 5V max.)
B: 3K3/680 Ohm switched
output
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680
 
output
OUT2:
Output to fire routing
equipment (Fire brigade)
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.8 A
supervised (Supervision
at 5V max.)
B: 3K3/680 Ohm
switched output
OUT3:
Output to fire protection
equipment
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
OUT4:
Output to fault warning
routings equipment
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output