FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 31
6.2.3 Supervised outputs A
These outputs provide 24 VDC when active. A red LED displays the state of the outputs.
(Refer to sections 3.2.1 and 3.2.3 for technical information on these outputs.)
Figure 20: Supervised relay output’s connection on SD2000 common I/O board
1. Fault routing (Out4)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
* Active in normal position
3. Fire routing device (Out2)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
2. Fire protection device (Out3)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
4. Fire alarm device (Out1)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
6.2.4 Relay outputs B
OUT1 / OUT2 / OUT3 (Refer to positions 7, 8, 9 in figure 13.)
Two configurations are available. The configuration is determined by jumper settings.
An LED indicates the state of the output (LED ON = output active).
Figure 21: Two configurations for relay outputs 1-3 B
Outputs CONFIG. 1 CONFIG. 2
Sounders OUT 1 J12 in
J13 out
J12 out
J13 in
" J18 out
J19 out
Fire Brigade OUT 2 J2 in
J3 out
J2 out
J3 in
" J18 out
J19 out
Fire Protection OUT3 J4 in J4 out