14 FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
3.2.4 Panel Operation
Battery operation - Normal operation
(No mains power)
FP12XX FR1200/FR2000 FP1216EN & FP1264
Current required by system 200 mA (max) 200 mA (max) 200 mA (max)
Loop current
- 2 loops
- 127 devices/loop @ 340 µA/device (DP951)
86 mA
0 mA
86 mA
Auxiliary current 0 mA 0 mA 0 mA
Total normal current 286 mA 200 mA 286 mA
Battery Operation - Alarm Operation
(No mains power)
FP12XX FR1200/FR2000 FP1216EN & FP1264
Normal current (as above) 286 mA (max) 200 mA (max) 286 mA (max)
Extra loop current (20 x LED @ 4 mA) 80 mA 0 mA 80 mA
Sounders (Sounder board: Outputs 1-4) 200 mA 0 mA 200 mA
Total alarm current 566 mA 200 mA 566 mA
Normal Operation FP2416/2464 & FP2432/24128 FP2864, FP28255
Mains load (maximum) 200 VA 200 VA
Total output current (27.6 V) 4 A 4 A
Battery capacity I
AUX
= 0 (72H standby) 36 AH 58 AH
Battery capacity (maximum) 69 AH 69 AH
Required battery charging current
(Maximum battery capacity)
3.05 A 3.05 A
Current required by system (I
SYS
)* 0.5 A 0.8 A
Available auxiliary current 0.45 A 0.15 A
Alarm Operation FP2416/2464 & FP2432/24128 FP2864, FP28255
Mains load (maximum) 200 VA 200 VA
Total output current (27.6 V) 4 A 4 A
Required battery charging current
(Maximum battery capacity)
0 A 0 A
Current required by system 0.6 A 1 A
Available auxiliary current 3.4 A 3 A
*I
SYS
calculated at 252 x 900 series ionisation detectors (FP2416/64) 1008 x 900 series ionisation detectors
(FP2864/255)
Charging current based to charge batteries up to 80% in 24 hours at 75% efficiency